Feature
Input Side
|
|
|||
Max. DC Input Power (kW)
|
78
|
91
|
97.5
|
104
|
Max. DC Input Voltage (V)
|
1000
|
|||
Start-up DC Input Voltage (V)
|
250
|
|||
MPPT Operating Range (V)
|
200-850
|
|||
Max. DC Input Current (A)
|
40+40+40+40
|
|||
Max. Short Circuit Current (A)
|
60+60+60+60
|
|||
No.of MPP Trackers
|
4
|
|||
No.of Strings per MPP Tracker
|
3+3+3+3
|
4+4+4+4
|
||
Output Side
|
|
|||
Rated Output Power (kW)
|
60
|
70
|
75
|
80
|
Max. Active Power (kW)
|
66
|
77
|
82.5
|
88
|
Rated Output Voltage/Range (V)
|
3L/N/PE 220/380V, 230/400V 0.85Un-1.1Un (this may vary with grid standards)
|
|||
Rated Grid Frequency (Hz)
|
50 / 60 (Optional)
|
|||
Operating Phase
|
Three Phase
|
|||
Rated AC Grid Output Current (A)
|
90.9/87
|
106.1/101.5
|
113.6/108.7
|
121.2/115.9
|
Max. AC Output Current (A)
|
100/95.7
|
116.7/111.6
|
125/119.6
|
133.3/127.5
|
Output Power Factor
|
0.8 leading to 0.8 lagging
|
|||
Total Harmonics Current Distortion (THDi)
|
<3%
|
|||
DC Injection Current (mA)
|
<0.5%
|
|||
Grid Frequency Range
|
45~55 or 55~65 (Optional)
|
|||
Efficiency
|
|
|||
Max. Efficiency
|
98.7%
|
|||
Euro Efficiency
|
98.3%
|
|||
MPPT Efficiency
|
>99%
|
|||
Protection
|
|
|||
DC Reverse-Polarity Protection
|
Yes
|
|||
AC Short Circuit Protection
|
Yes
|
|||
AC Output Overcurrent Protection
|
Yes
|
|||
Output Overvoltage Protection
|
Yes
|
|||
Insulation Resistance Protection
|
Yes
|
|||
Ground Fault Monitoring
|
Yes
|
|||
Anti-islanding Protection
|
Yes
|
|||
Temperature Protection
|
Yes
|
|||
Integrated DC Switch
|
Yes
|
|||
Remote Software Upload
|
Yes
|
|||
Remote Change of Operating Parameters
|
Yes
|
|||
Surge Protection
|
DC Type II / AC Type II
|
|||
General Data
|
|
|||
Cabinet Size (WxHxD mm)
|
700×575×297 (Excluding Connectors and Brackets)
|
|||
Weight (kg)
|
60
|
|||
Topology
|
Transformerless
|
|||
Internal Consumption
|
<1W (Night)
|
|||
Running Temperature
|
-25-65℃, >45℃ Derating
|
|||
Ingress Protection
|
IP65
|
|||
Noise Emission (Typical)
|
≤50 dB
|
≤55 dB
|
||
Cooling Concept
|
Smart Cooling
|
|||
Permissible Altitude (m)
|
2000
|
|||
Warranty
|
5 Years
|
|||
Grid Connection Standard
|
IEC 61727, IEC 62116, CEI 0-21,CEI 0-16,EN 50549, NRS 097, RD 140, UNE 217002,
OVE-Richtlinie R25, G99, VDE-AR-N 4105, VDE-AR-N 4110
|
|||
Operating Surroundings Humidity
|
0-100%
|
|||
Safety EMC / Standard
|
IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2
|
|||
Features
|
|
|||
Display
|
LCD1602
|
|||
Interface
|
RS485/RS232/Wifi/LAN
|
Certification